Series 47
Intrinsically Safe Alarm Panel Control, 4-Channel
|

|

 |
Solid State
Reliability |
 |
0-50K Ohm/cm
Sensitivity |
 |
Alarm
Contacts for Audible and Visual Alarms |
 |
4 Channel
Relay |
 |
Removable
Terminal Strips |
 |
Inverse or
Direct Acting Field Selectable |
 |
U.L.
Recognized |
Series 47
intrinsically safe controls offer complete alarm panel control in a
single package. Powered output contacts allow quick connection of
lights and audible alarms. Test and silence functions are built in.
Unit also carries one SPDT master alarm contact for remote alarm
activation. Approved for Class I, II, III, Division 1, Groups C, D,
E, F, G hazardous atmospheres, Series 47 controls supply four
channels which can be used with conductivity-based liquid level
sensors or dry contact sensors. This device functions as an alarm or
single point control. Field adjustable for direct or inverse
operation, it can operate separate visual alarms with a common
audible alarm channel. Silence and test terminals are standard. For
additional lights, alarms or outputs, auxiliary contacts must be
ordered.
Typical Applications:
 |
Hazardous
Locations |
 |
Monitoring
and Control |
 |
Storage Tank
Alarm Panel |
 |
Input for
Computer |
 |
Input for
Phone Dialer |
|
Specifications:
|
Contact
Design |
SPDT 1 N.O. &
1 N.C. |
|
Master
Alarm Contact Rating (30VDC, 120/240VAC) |
5 A
Resistive, 1/10 hp |
|
Indicator
Contacts |
Powered 120
VAC 25mA |
|
Indicator
Contacts for Audible Alarm |
Powered 120
VAC 5A |
|
Auxiliary
Contacts (optional) |
SPDT 120 VAC
10A (not powered) |
|
Sensitivity |
0-50K Ohm
maximum specific resistance |
|
Primary
Voltage |
30 VDC, 120
VAC, 240 VAC (+10%/-15%), 50/60 Hz |
|
Secondary
Voltage |
12 VAC @ 6mA
RMS |
|
Temperature |
-40°F to
150°F |
|
Approvals |
U.L. 913 File
# ES7112 Vol. 1, Sec. 2; CSA (optional) |
|
|