The Replacement Components for
the Warrick Series 1 and Series 2 Controls comes in two flavors, the
Retro-Fit Components and the DIN-Mount Components. The Retro-Fit Components
can be used in any Series 1 or Series 2 Warrick Enclosure. The DIN-Mount
Components can be used in Warrick NEMA 4 & NEMA 7/9 Enclosures. It does not
fit in the Warrick NEMA 1 Enclosure. |
|
Retro-Fit Assembly and Components: Shown Below
 |
DIN-Mount Assembly and Components: Shown Below
 |
|
Model Retro-Fit Components
 |
Retro-Fit Plate to fit
Warrick Series 1 & Series 2 Mounting Holes. Accommodates Relay Socket,
Relay & Series 26M Octal Socket Components. |
 |
10A 3PDT Relay (UL Recognized
file E41643, CSA Certified file LR31928. |
 |
UL Relay Socket. (UL E87929,
CSA LR31928) |
 |
UL 11-Pin Octal Socket for
Series 26M Control. (UL E60008, CSA LR29513) |
 |
Specify a Series 26M to suit
your application, sold separately. Rated U.L. 353 File # MP1430 as LIMIT
CONTROL |
|
Model DIN-Mount Components
 |
DIN Rail Accommodates Relay
Socket, Relay and Series 26M Octal Socket Components. Not for use in
Warrick NEMA 1 Enclosure. |
 |
10A 3PDT Relay (UL
Recognitized file E41643, CSA Certified file LR31928. |
 |
UL Relay Socket. (UL E87929,
CSA LR31928) |
 |
UL 11-Pin Octal Socket for
Series 26M Control. (UL E60008, CSA LR29513) |
 |
Specify a Series 26M to suit
your application, sold separately. Rated U.L. 353 File # MP1430 as LIMIT
CONTROL |
|
|
Application Considerations:
 |
The Retro-Fit Components and
the DIN-Mount Components each have a 10A Relay rated at 1/2 HP with
LED
Indication while the Warrick Series 1 and Series 2 had 16A Relays rated 1
HP with no LED Indication. |
 |
Series 26M Control has Reset
Button capability and optional Power Outage Feature which automatically
resets the Series 26M to regular operation if water is present to LLCO
Probe after Power Outage. The old Series 1 and Series 2 would have to be
manually reset even if LLCO had water present. |
 |
The Series 26M has a much
wider Sensitivity Range to order from: 4.7K to 100K. |
 |
The Series 26M is available
with either 24 VAC, 120 VAC, 240 AC, or 208/240 VAC. Note: The 240
VAC and the 208/240 VAC do not carry UL Limit Control Recognition. |
 |
The Series 26M Series has
standard 3 Second built in time delay which reduces effects of turbulence. |
 |
The Series 26M Solid State
has LED
Indication and meets CSD1 Requirements. |
 | The Series 26M has Low Probe Voltage at 12 VAC
eliminating shock hazard present with the Old Warrick Series 1 Controls. |
|
| For Complete
Information: PDF
Retro-Components |
For Series 1 or Series 2 Replacement use
either the Retro-Fit Components or the DIN-Mount Components and a Series 26M
Control. In most applications with a 120 VAC Power use one of the
Components Kits with a 26MC1M0-F |